The 42001-NEL thermostat is ideal for applications where freeze protection or lowerrange temperature control is critical. In cold climates the thermostat switches heating devices that prevent pipes, valves, tanks and fittings from freezing.
This thermostat can be used in ambient-sensing applications by placing the sensor in the air or as a line-sensing thermostat by securing the bulb to the pipe or tank. It can be used as a single circuit control or as a pilot control for several circuits by switching a contact. Set point at factory is 40 degrees F (5C).
Enclosure Rating
NEMA 4X
Entries
One ¾ inch NPT conduit hub
Set Point
40 °F (5 °C) Close on decreasing temperature
Sensor exposure limits
-30 to 140 °F (-35 to 60 °C)
Enclosure material
Polycarbonate black
Switch
SPD, prewired snap action
Electrical rating
22 amp@ 125/250/480 VAC
Accuracy
±1% of full scale
Sensor & capillary type
Copper tin plated, Silicone oil filled bulb3.12” (79mm) .39” (10mm) diameter10’ (3.05m) long capillary
Connection
14 AWG stranded copper wire, PVC
Approvals
CSA and UL Listed (Ordinary Areas)
Manufacturer
Nelson
10 Foot Pig-Tail Power Cord w/Molded Plug
Product code: EPT-10
20 AMP 30mA GFCI Plug Kit
120VAC code: EGFI-120
240VAC code: EGFI-240